- M-Bus or wireless M-Bus. In connection with Diehl Metering AMR systems technology, an unbeatable transmission performance is possible
- Constantly high measuring rate (flow: 2 s; temp.: 16 s) at up to 12 years battery life. The current output is calculated every 2 seconds
- AA batteries with low lithium content (0.7 g per piece) as A batteries
- Battery contacts corrosion protection, without spring contacts
- MID class 2 and PTB K7.2
- MID electromagnetic class E2 and mechanical class M2, which makes it less sensitive to sources of interference (e.g. frequency-controlled PWM pumps)
- Removable 8-digit LCD computer
Compact energy counter | ultrasound – SHARKY 774 COMPACT
0,00 €
zzgl. Versandkosten
Ultrasound compact energy counter SHARKY 774 COMPACT
The ultrasound compact energy counter can be used to record all data relevant to billing and measuring the energy consumption of heating and cooling systems. The measurement principle is static. The ultrasound measurement principle offers many advantages: No moving parts (less wear and tear and fouling of the counter), lower pressure loss, a high degree of dynamic measuring and a lower start-up value, resistant to loose parts.
Brand |
Diehl |
---|
Technical data
Application | Heating - cooling - heating/with cooling rate |
Approval | MID (DE-13-MI004-PTB008) and PTB K7.2 for cooling (DE-16-M-PTB-0041) |
Environmental class | Class C |
Environmental class | Class E2 + M2 |
Environmental temperature during operation °C | +5 ... +55 (<35 °C has a positive effect on the life span) |
Storage temperature °C | -25 ... +60 (>35 °C max. 4 weeks) |
Communication | M-Bus or radio |
Frequency band | 868 or 434 MHz |
Type radio telegram | Open Metering Standard (OMS) |
Data currency | Online - no time delay between the measured value collection and data transfer |
Data transfer | Unidirectional |
Transmission interval | Rapid Modus (Drive-by): 14 s + Synchron Telegramm: 900 s | Standard Modus (Walk-by): 64 |
Testing options | Via display, visual test impulses |